The FF6 has field-selectable, built-in strobe and horn sync protocols. In the event of a NAC fault, the FF6 can be configured to notify the FACP. Gamewell's FF6 provides independent output circuit supervision. The FF6 includes an internal battery charger. The outputs may be configured as: four Class B (Style W, X, Y) or two Class A (Style Z) or two Class B and one Class A. Each NAC is rated at 3.0 Amp maximum, with a total output capacity of 6.0 Amp. Designed with advanced switchmode power-supply technology, the FireForce 6 provides filtered and electronically-regulated power distributed to four NACs. The FF6 will connect to any brand of UL-Listed Fire Alarm Control Panel (FACP) to provide Notification Appliance Circuit expansion. The FireForce 6 (FF6) from Gamewell is a Notification Appliance Circuit (NAC) extender panel designed to extend the power capabilities of existing NACs and provide power (3.0 A maximum) for other ancillary devices. Facilitates multiple NAC synchronization for large areas.įield-Selectable NAC Signaling INPUT Steady Sync OUTPUT (follows input) Temporal Steady Sync Steady with noise eliminated Sync Isolated AC Fail Form-C relay, immediate or delayed six hours. 6.0 Amp, 24 VDC, fully regulated full-load output (power-limited). Four configurable supervised NAC outputs. Multiple sync protocols, compatible with the following appliances: CooperWheelock, Faraday, System Sensor, and Gentex as field-selectable options. Provides two fully-supervised input/ control circuits 32 VDC).